08 Adequate handwashing sinks properly supplied and accessible |
in |
|
|
|
0 |
08 0080-04-09-.05(2)(c)1 Handwashing sinks are installed according to the capacity of preparation areas |
out |
A splash guard needs to be installed at the hand washing sink in the front food service area. |
|
Priority Foundation (PF) |
0 |
08 0080-04-09-.05(2)(e)1 Handwash sink shall only be used for washing hands; accessible at all times |
out |
Hand washing sink at the back food service area was observed to be inaccessible. |
Person in charge removed papers and other items from hand washing sink at the back service food area. |
Priority Foundation (PF) |
0 |
08 0080-04-09-.06(3)(a)3 Handwashing sinks, properly supplied with drying devices |
out |
The hand washing sink at the back food service area was observed to not have drying device or paper towels available for use. |
|
Priority Foundation (PF) |
0 |
33 Thermometers provided and accurate |
in |
|
|
|
0 |
33 0080-04-09-.04(2)(d)9 Temperature Measuring Devices shall be located in hot and cold holding units; easily readable |
out |
The TCS front cold holding unit and the isolated cold holding milk unit were observed to not have any temperature measuring devices. |
|
Priority Foundation (PF) |
0 |
42,43 Single service & gloves |
in |
|
|
|
0 |
42,43 42 Single-service articles stored and used |
in |
|
|
|
0 |
42,43 0080-04-09-.04(9)(c)1 Single-service articles protected from contamination |
out |
Single use corn dog sleeves were observed to be stored uncovered and not inverted. |
|
Core (C) |
0 |
44,45 Utensils and equipment |
in |
|
|
|
0 |
44,45 45 Warewashing facilities installed, maintained, and used; test strips |
in |
|
|
|
0 |
44,45 0080-04-09-.04(2)(d)16 Warewashing sink, drainboards, and warewashing machines shall be self-draining |
out |
No drainboards or drying racks were present at the three compartment sink. |
|
Priority Foundation (PF) |
0 |
44,45 0080-04-09-.04(3)(b)4 Test Kits to measure concentration of sanitizing solutions. |
out |
No test Quat sanitizer strip were available for use. |
|
Priority Foundation (PF) |
0 |
50 Toilet facilities; constructed, supplied, cleaned |
in |
|
|
|
0 |
50 0080-04-09-.06(5)(h) Toilet room cleaning frequency |
out |
Men's restroom was observed to have excessive amount of buildup on the sink, toilet, and floor. There was also a strong urine smell. |
|
Core (C) |
1 |
51,52 Facilities |
in |
|
|
|
0 |
51,52 52 Physical facilities installed, maintained, clean |
in |
|
|
|
0 |
51,52 0080-04-09-.06(5)(b) Physical facilities shall be cleaned as often as necessary |
out |
The fan guard in the walk in cold holding unit had excessive amount dust. The floor in the walk-in cold holding unit had excessive amount of dried food residues and build up. |
|
Core (C) |
0 |